HGA 5% Active Harmonic Filter
TMS & TCI for over 16 years the difference in service and power quality solutions for the canadian market.
Hybrid Power Quality Solutions using Line Reactors, Active and Passive Harmonic Filters
Harmonic Distortion in Data Centers. Power Quality and Power Reliability are critical to data center operation.
Active Harmonic Filters Brochure
HGA 5% Active Harmonic Filter
Actively limits Harmonic Distortion
-
TDD reduction to 5% or better at Full Load
-
Meets IEEE-519 2014
-
Improves true power factor - improves energy efficiency
-
System-applied - MCC & Switchboard
-
Touchscreen display
-
UL 508 Certified. No SCCR required by UL Standards for the filter.
-
Communication options include Modbus RTU over RS485, EtherNet/IP, Modbus TCP/IP and DeviceNet.
Fits in Narrow Spots
In a tight spot? The HGA configuration minimizes the space required for harmonics mitigation in the electrical equipment line up, maximizing building space for more productive uses. For example, our 200 A HarmonicGuard Active filter has been re-engineered to have the same form factor as our popular HGA 250 A and suitable for single door MCC integration.
New features available
New capabilities are available on the already high-performing Active Harmonic Filter product family. This latest release includes additional functionality which allows the HGA to operate in a wider variety of applications and to solve a broader array of harmonic problems.
|
The HGA Active Line Conditioner
The HGA active harmonic filter actively monitors the load current, reacting to changes in load almost instantaneously, while returning true power factor to near unity:
-
Virtual real time correction of the non-linear current
-
Synchronization of the current and voltage waveforms
-
Always attempting to achieve unity power
-
Never allowing for leading power factor
|
HMI Display Video
Fully featured 6", 65k color touchscreen HMI display.
|
|
Harmonics and Power Quality
Variable frequency drives and other types of non-linear loads take the incoming power from the utility and modify it for more efficient use within a wide range of applications. The conversion process creates current and voltage distortion.
If non-linear loads represent a significant portion of the entire installed load, this distortion begins to cause problems throughout the electrical system:
Performance
Non-linear Load Waveform |
|
Resulting Line Current Waveform with HGA |
|
|
|
Unfiltered waveform with Injection Current from the HGA |
|
|
By actively monitoring the line or load current, the HGA harmonic filter determines the nature and quantity of harmonic currents in the system and cancels the same by injecting equal amounts of harmonic currents opposite in phase. A state-of-the-art high speed DSP controller and a pulse width modulated (PWM) IGBT based power converter help to provide virtual real time compensation of non-linear load demanded by VFDs and other applications. HGA also inherently tries to synchronize the line current with its voltage resulting in near unity displacement power factor. Thus, HGA provides solutions for both reactive current and harmonic current compensation.
Meeting IEEE-519 Recommendations on Harmonics
The HGA active filter provides a cost effective, efficient solution allowing the user to meet IEEE-519 requirements. Using harmonic analysis software, TMS can help customers meet IEEE-519. Typical applications include:
HGA Filters versus Other Harmonic Solutions
The HGA active filter can be a better overall system solution when compared to large, expensive 18 pulse VFDs or multiple passive drive-applied filtering:
-
Save money
-
Save space
-
Reduce energy losses
Bus-Applied Configuration for MCC or Switchboard
This bus-applied filter design can be directly connected to the power bus in standard MCC and Switchboard configurations. As with other bus-applied designs, impedance must be installed on the load side of the HGA filter.
Product Specifications
-
TDD Reduction to 5% or better at Full Load
-
Power Factor Correction to less than or equal to .98 lagging
-
Power Factor Improved to near Unity
-
Response time of less than 8 ms to step load changes
-
Additional filters can be added to increase correction capability
-
Units can be paralleled without any calibration
-
Self-Commissioning Installation
-
Modular design
-
Harmonic Cancellation to the 50th harmonic
The HGA active harmonic filter is a very sophisticated, stable, and effective solution for harmonic and reactive power compensation.
IEEE Standard 519-2014
Table 2 - Current distortion limits for systems rated 120 V through 69 kV
Maximum harmonic current distortion in percent of IL |
Individual harmonic order (odd harmonics) a, b |
ISC/IL |
3≤h<11 |
11≤h<17 |
17≤h<23 |
23≤h<35 |
35≤h≤50 |
TDD |
<20c |
4.0 |
2.0 |
1.5 |
0.6 |
0.3 |
5.0 |
20<50 |
7.0 |
3.5 |
2.5 |
1.0 |
0.5 |
8.0 |
50<100 |
10.0 |
4.5 |
4.0 |
1.5 |
0.7 |
12.0 |
100<1000 |
12.0 |
5.5 |
5.0 |
2.0 |
1.0 |
15.0 |
>1000 |
15.0 |
7.0 |
6.0 |
2.5 |
1.4 |
20.0 |
aEven harmonics are limited to 25% of the odd harmonic limits above.
bCurrent distortions that result in a dc offset, e.g., half-wave converters, are not allowed.
cAll power generation equipment is limited to these values of current distortion, regardless of actual ISC/IL.
where
ISC = maximum short-circuit current at PCC
IL = maximum demand load current (fundamental frequency component) at the PCC under normal load operating conditions.